HP TRANSFORMER OIL is designed for human safety and free from carcinogenic Poly chlorinated Bi-phenyls (PCB) and Poly aromatic hydrocarbon (PAH).
- Electric transformers
 - Switch gears
 - Circuit breakers which require insulating fluids
 - Has very high oxidation stability
 - Excellent ageing properties resulting in long product life
 
HP TRANSFORMER OIL exceeds IS: 335:1993 (Reaffirmed 2005) performance levels. It also meets IS:335-2018 TYPE II UNINHIBITED.
Physico-Chemical properties
| PROPERTIES | HP TRANSFORMER OILS | 
| Appearance | Clear and transparent and free from suspended matter of sediments | 
| Density at 29.5 ºC, g/cc | 0.8279 | 
| Kinematic viscosity, cstAt 27ºCAt 40ºC | 16.4611 | 
| Interfacial tension at 27ºC | 0.044 N/m | 
| Flash point pensky-marten (closed),ºC | 172 | 
| Pour point,ºC | -18 | 
| Neutralization value, mg KOH/ga) Total acidityb) Inorganic acidity/alkalinity | NilNil | 
| Corrosive sulphur | Non corrosive | 
| Electric strength (breakdown voltage) –kV(rms)a) New unfiltered oil | 72 | 
| Dielectric dissipation factor at 90 ºC | 0.00025 | 
| Specific resistance (resistivity)a) A:90 ºCb) A:27 ºC | 750x1012 ohm-cm11300x1012 ohm-cm | 
| Oxidation stabilitya) Neutralization value after oxidation, mg KOH/gb) Total sludge after oxidation,% by wt. | 0.40.1 | 
| AGEING CHARACTERISTICS AFTER AGEING | |
| Open breaker method with copper characteristics | |
| Specific resistance (resistivity)a) A:27 ºCb) A:90 ºCc) dielectric dissipation factor at 90 ºCd) total aciditye) total sludge | 350x1012 ohm-cm19x1012 ohm-cm0.0025/2.08 DCNILNIL | 
| Presence of oxidation inhibitor,% by wt | Absent | 
| Water content, mg/kg(ppm) | 50 | 
| SK value (%) | 1 |